Product Details

1. CT analyser Brief Introduction

This portable Automatic Current Transformer Testing Equipment CT PT Analyzer allows performing many different measurements such as saturation, ratio and polarity tests and CT winding resistance test. Substation maintenance and commissioning test equipment, CTA-1000 Series CT Analyzer is extremely appreciated by electrical engineers for its high accuracy and portability.


2. Product Parameters

Type

CTA-1000C

Test standards

GB1208(IEC60044-1)、GB16847(IEC60044-6) 、GB1207

Power supply

AC220V±10%,50Hz

Output

0~180Vrms,12Arms,36A(peak value)

Voltage measurement accuracy

±0.1%

CT Ratio

Range

1~40000

accuracy

±0.05%

PT Ratio

Range

1~40000

accuracy

±0.05%

Phase

Range

±2min

accuracy

0.5min

DC resistance

Range

0~300Ω

accuracy

0.2%±2mΩ

Burden

Range

0~1000VA

accuracy

0.2%±0.02VA


AC220V±10%,50Hz

Environmental Conditions

Operating temperature : -10οC~50οC
Humidity :≤90%

Weight and Dimensions

Dimensions: 365 mm×290mm×153mm;
Weight<9kg


3. Product Features

1. Wide range of Measurement

Current Transformer (CT)

Voltage Transformer (PT)

CT ratio and phase-angle accuracy

PT excitation and saturation

CT accuracy for different burdens

Burden impedance

CT winding resistance

PT polarity

CT inductance (saturated and unsaturated)

Winding resistance Saturated and non-saturated inductance

CT excitation characteristics

ALF and FS (direct and indirect)

Burden impedance

CT residual magnetism

2. Easy to use. The CT Analyzer allows all types of single and multi-ratio current transformers to be tested, and it evaluates the current transformer within seconds with the push of a button;

3. Highest measurement accuracy: 0.05% / 2 min when calibrating on site;

4. Automatic evaluation according to IEC and IEEE standards;

5. CT analyzer debugging time is short (automatic test duration <2 minutes);

6. Excellent workplace safety - Tests run at max. 180V;

7. Very small and lightweight (< 9kg/19.8lbs), easy to transport for on-site testing;

8. The CT analyzer has a professional pull box design that is easy to carry and resistant to vibration.